首次上传
This commit is contained in:
@@ -0,0 +1,286 @@
|
||||
using System.Collections.Generic;
|
||||
using System.Diagnostics;
|
||||
using Aitex.Core.RT.Device;
|
||||
using Aitex.Core.RT.Device.Devices;
|
||||
using Aitex.Core.RT.Event;
|
||||
using Aitex.Core.RT.Routine;
|
||||
using Aitex.Core.RT.SCCore;
|
||||
using MECF.Framework.Common.Equipment;
|
||||
using SicModules.PMs.Routines.Base;
|
||||
|
||||
namespace SicModules.PMs.Routines
|
||||
{
|
||||
public class PMVacIdleRoutine : PMBaseRoutine
|
||||
{
|
||||
private enum RoutineStep
|
||||
{
|
||||
RotationEnable,
|
||||
HeatEnable,
|
||||
VentPumpClose,
|
||||
ArSupply,
|
||||
|
||||
SetGroupB,
|
||||
SetGroupC,
|
||||
SetGroupE,
|
||||
SetGroupF,
|
||||
SetGroupH,
|
||||
SetGroupD,
|
||||
SetGroupG,
|
||||
SetGroupK,
|
||||
SetGroupJ,
|
||||
|
||||
SetM1to16,
|
||||
SetM17M18,
|
||||
SetPC,
|
||||
SetGroupI, //V87-96
|
||||
SetM18,
|
||||
SetM2to40,
|
||||
SetM2to40_1,
|
||||
MfcAll,
|
||||
|
||||
SetGasOut,
|
||||
SetTv,
|
||||
SetTv1,
|
||||
WaitTv1,
|
||||
|
||||
SetGasIn1, //V65,V67,V68
|
||||
OpenFinal1, //V91-96
|
||||
SetMfcFinal1, //M32-38
|
||||
|
||||
SetGasIn2,
|
||||
SetGroupJOpen,
|
||||
|
||||
OpenFinal2,
|
||||
SetMfcFinal2,
|
||||
|
||||
PumpDownTimeout,
|
||||
SetTvMode,
|
||||
|
||||
SetEPV1,
|
||||
SetEPV2,
|
||||
SetTVEnable,
|
||||
SetTVPressMode,
|
||||
SetTvPositionToZero,
|
||||
SetMFCMode,
|
||||
SetPCMode,
|
||||
|
||||
SetTvOpen,
|
||||
SetTvModeToPress,
|
||||
SetTVto1050,
|
||||
OpenGasIn1,
|
||||
SetV65,
|
||||
CloseGasIn1,
|
||||
CloseFinanl1,
|
||||
CloseFinanl2,
|
||||
SetGroupV38,
|
||||
|
||||
SetV76,
|
||||
SetV75,
|
||||
SetGroupV25,
|
||||
SetV31,
|
||||
SetV32,
|
||||
SetV35V36,
|
||||
SetV87V97,
|
||||
SetV103,
|
||||
SetV105,
|
||||
SetTVPositionMode,
|
||||
SetTVPositionMax,
|
||||
|
||||
CloseM32M35M37,
|
||||
CloseM36,
|
||||
CloseM38,
|
||||
|
||||
TimeDelay1,
|
||||
TimeDelay2,
|
||||
TimeDelay3,
|
||||
TimeDelay4,
|
||||
TimeDelay5,
|
||||
TimeDelay6,
|
||||
TimeDelay7,
|
||||
TimeDelay8,
|
||||
TimeDelay9,
|
||||
TimeDelay10,
|
||||
TimeDelay11,
|
||||
TimeDelay12,
|
||||
TimeDelay13,
|
||||
TimeDelay14,
|
||||
}
|
||||
|
||||
private PMModule _pm1Module;
|
||||
private IoThrottleValve2 _IoThrottle;
|
||||
private IoInterLock _pmIoInterLock;
|
||||
|
||||
private int _rotationCheckSpeed = 0; //设置旋转速度为0后检查是否转速低于此数值
|
||||
private int _rotationCloseTimeout; //旋转停止超时
|
||||
private int _IoValueOpenCloseTimeout = 10; //开关超时时间
|
||||
private int _heatTimeOut = 5; //Heat关闭等待Di反馈超时时间
|
||||
|
||||
private double _pmPressureMaxDiff; //蝶阀与目标压力的差值范围(认为调整到位了)
|
||||
private int _throttleTimeout; //蝶阀调整到指定压力的超时时间
|
||||
|
||||
private double _vacPumpBasePressure;
|
||||
private int _routineTimeOut;
|
||||
private int _pumpTimeOut;
|
||||
|
||||
private Stopwatch _swTimer = new Stopwatch();
|
||||
public PMVacIdleRoutine(ModuleName module, PMModule pm1) : base(module, pm1)
|
||||
{
|
||||
Module = module.ToString();
|
||||
_pm1Module = pm1;
|
||||
Name = "VacIdle";
|
||||
|
||||
_IoThrottle = DEVICE.GetDevice<IoThrottleValve2>($"{Module}.TV");
|
||||
_pmIoInterLock = DEVICE.GetDevice<IoInterLock>($"{Module}.PMInterLock");
|
||||
}
|
||||
|
||||
public override Result Start(params object[] objs)
|
||||
{
|
||||
Reset();
|
||||
|
||||
_rotationCloseTimeout = SC.GetValue<int>($"PM.{Module}.RotationCloseTimeout");
|
||||
_pmPressureMaxDiff = SC.GetValue<double>($"PM.{Module}.ThrottlePressureMaxDiff");
|
||||
_throttleTimeout = SC.GetValue<int>($"PM.{Module}.ThrottlePressureTimeout");
|
||||
|
||||
_vacPumpBasePressure = SC.GetValue<double>($"PM.{Module}.Pump.PumpBasePressure");
|
||||
_routineTimeOut = SC.GetValue<int>($"PM.{Module}.Pump.RoutineTimeOut");
|
||||
_pumpTimeOut = SC.GetValue<int>($"PM.{Module}.Pump.PumpTimeOut");
|
||||
|
||||
if (!_pmIoInterLock.SetPMVacIdleRountingRunning(true, out var reason))
|
||||
{
|
||||
EV.PostAlarmLog(Module, $"can not run VACIdle, {reason}");
|
||||
return Result.FAIL;
|
||||
}
|
||||
|
||||
_swTimer.Restart();
|
||||
Notify("Start");
|
||||
return Result.RUN;
|
||||
}
|
||||
|
||||
public override Result Monitor()
|
||||
{
|
||||
try
|
||||
{
|
||||
CheckRoutineTimeOut();
|
||||
|
||||
//关闭V76,打开V75
|
||||
SetIoValueByGroup((int)RoutineStep.SetV76, IoGroupName.V76, false, _IoValueOpenCloseTimeout);
|
||||
SetIoValueByGroup((int)RoutineStep.SetV75, IoGroupName.V75, true, _IoValueOpenCloseTimeout);
|
||||
|
||||
//旋转停止,加热停止
|
||||
SetHeatEnable((int)RoutineStep.HeatEnable, false, _heatTimeOut);
|
||||
SetRotationValve((int)RoutineStep.RotationEnable, _rotationCheckSpeed, false, _rotationCloseTimeout);
|
||||
|
||||
//关闭V72,打开V25
|
||||
SetIoValueByGroup((int)RoutineStep.VentPumpClose, IoGroupName.VentPump, false, _IoValueOpenCloseTimeout);
|
||||
SetIoValueByGroup((int)RoutineStep.SetGroupV25, IoGroupName.V25, true, _IoValueOpenCloseTimeout);
|
||||
//打开V103,关闭V105
|
||||
SetIoValueByGroup((int)RoutineStep.SetV103, IoGroupName.V103, true, _IoValueOpenCloseTimeout);
|
||||
SetIoValueByGroup((int)RoutineStep.SetV105, IoGroupName.V105, false, _IoValueOpenCloseTimeout);
|
||||
|
||||
//打开V31,打开V32
|
||||
SetIoValueByGroup((int)RoutineStep.SetV31, IoGroupName.V31, true, _IoValueOpenCloseTimeout);
|
||||
SetIoValueByGroup((int)RoutineStep.SetV32, IoGroupName.V32, true, _IoValueOpenCloseTimeout);
|
||||
|
||||
//打开V35,打开V36
|
||||
SetIoValueByGroup((int)RoutineStep.SetV35V36, IoGroupName.V35V36, true, _IoValueOpenCloseTimeout);
|
||||
|
||||
//关闭B/C/E/F/H/K 阀门
|
||||
SetIoValueByGroup((int)RoutineStep.SetGroupB, IoGroupName.B, false, _IoValueOpenCloseTimeout);
|
||||
SetIoValueByGroup((int)RoutineStep.SetGroupC, IoGroupName.C, false, _IoValueOpenCloseTimeout);
|
||||
SetIoValueByGroup((int)RoutineStep.SetGroupE, IoGroupName.E, false, _IoValueOpenCloseTimeout);
|
||||
SetIoValueByGroup((int)RoutineStep.SetGroupF, IoGroupName.F, false, _IoValueOpenCloseTimeout);
|
||||
SetIoValueByGroup((int)RoutineStep.SetGroupH, IoGroupName.H, false, _IoValueOpenCloseTimeout);
|
||||
SetIoValueByGroup((int)RoutineStep.SetGroupK, IoGroupName.K, false, _IoValueOpenCloseTimeout);
|
||||
|
||||
//打开D/G 阀门
|
||||
SetIoValueByGroup((int)RoutineStep.SetGroupD, IoGroupName.D, true, _IoValueOpenCloseTimeout);
|
||||
SetIoValueByGroup((int)RoutineStep.SetGroupG, IoGroupName.G, true, _IoValueOpenCloseTimeout);
|
||||
|
||||
//设置MFC和PC的模式
|
||||
SetMfcModeToNormalByGroup((int)RoutineStep.SetMFCMode, MfcGroupName.All);
|
||||
SetPcModeToNormal((int)RoutineStep.SetPCMode, _lstPcList);
|
||||
|
||||
//M1-M16设定为default值(M2、M9、M15除外)
|
||||
SetMfcToDefaultByGroup((int)RoutineStep.SetM1to16, MfcGroupName.M1to16, 0);
|
||||
SetMfcToDefaultByGroup((int)RoutineStep.SetM17M18, MfcGroupName.M17M18, 0);
|
||||
|
||||
//M2、M9、M15、M19-M40 MFC 3s ramp 到 default值
|
||||
SetMfcToDefaultByGroup((int)RoutineStep.SetM2to40_1, MfcGroupName.M2toM42, 3);
|
||||
|
||||
//设置所有PC到默认值
|
||||
SetPcToDefault((int)RoutineStep.SetPC, _lstPcList);
|
||||
|
||||
//打开V68
|
||||
SetIoValueByGroup((int)RoutineStep.OpenGasIn1, IoGroupName.GasIn1, true, _IoValueOpenCloseTimeout);
|
||||
|
||||
//打开J阀门
|
||||
SetIoValueByGroup((int)RoutineStep.SetGroupJ, IoGroupName.J, true, _IoValueOpenCloseTimeout);
|
||||
|
||||
//打开V65
|
||||
SetIoValueByGroup((int)RoutineStep.SetV65, IoGroupName.V65, true, _IoValueOpenCloseTimeout);
|
||||
|
||||
//打开EPV2
|
||||
SetIoValueByGroup((int)RoutineStep.SetEPV2, IoGroupName.EPV2, true, _IoValueOpenCloseTimeout);
|
||||
TimeDelay((int)RoutineStep.TimeDelay5, 3);
|
||||
|
||||
//设置蝶阀Enable
|
||||
SetThrottleEnableAndWait((int)RoutineStep.SetTVEnable, _IoThrottle, 5);
|
||||
|
||||
//设置蝶阀为压力模式
|
||||
SetThrottleToPressModeAndWait((int)RoutineStep.SetTVPressMode, _IoThrottle, 5);
|
||||
|
||||
//伺服压力设定值到0mbar
|
||||
SetThrottleToTargetAndNoWait((int)RoutineStep.SetTv1, _IoThrottle, _vacPumpBasePressure);
|
||||
|
||||
//M2、M9、M15、M19-M40 MFC 3s ramp到0
|
||||
SetMfcByGroup((int)RoutineStep.SetM2to40, MfcGroupName.M2toM42, 0, 3);
|
||||
SetMfcByGroup((int)RoutineStep.SetM18, MfcGroupName.M18, 0, 3);
|
||||
//关闭V87 V97
|
||||
SetIoValueByGroup((int)RoutineStep.SetV87V97, IoGroupName.V87V97, false, _IoValueOpenCloseTimeout);
|
||||
|
||||
//等待腔体压力Pump到设定值
|
||||
WaitChamberPressDownTo((int)RoutineStep.WaitTv1, _vacPumpBasePressure, _pumpTimeOut);
|
||||
|
||||
//蝶阀设置为位置模式,开度设置为最大
|
||||
SetThrottleToPositionMode((int)RoutineStep.SetTVPositionMode, _IoThrottle, _throttleTimeout);
|
||||
SetThrottleSetPosition((int)RoutineStep.SetTVPositionMax, _IoThrottle, 100, _throttleTimeout);
|
||||
|
||||
}
|
||||
catch (RoutineBreakException)
|
||||
{
|
||||
return Result.RUN;
|
||||
}
|
||||
catch (RoutineFaildException)
|
||||
{
|
||||
return Result.FAIL;
|
||||
}
|
||||
|
||||
_pmIoInterLock.SetPMVacIdleRountingRunning(false, out string reason);
|
||||
Notify($"Finished ! Elapsed time: {(int)(_swTimer.ElapsedMilliseconds / 1000)} s");
|
||||
_swTimer.Stop();
|
||||
|
||||
return Result.DONE;
|
||||
}
|
||||
|
||||
public override void Abort()
|
||||
{
|
||||
_pmIoInterLock.SetPMVacIdleRountingRunning(false, out string reason);
|
||||
_pmIoInterLock.SetPMPumpRoutineRunning(false, out _);
|
||||
PmDevice.SetRotationServo(0, 0);
|
||||
|
||||
base.Abort();
|
||||
}
|
||||
|
||||
private void CheckRoutineTimeOut()
|
||||
{
|
||||
if (_routineTimeOut > 10)
|
||||
{
|
||||
if ((int)(_swTimer.ElapsedMilliseconds / 1000) > _routineTimeOut)
|
||||
{
|
||||
EV.PostAlarmLog(Module, $"Routine TimeOut! over {_routineTimeOut} s");
|
||||
throw (new RoutineFaildException());
|
||||
}
|
||||
}
|
||||
}
|
||||
}
|
||||
}
|
||||
Reference in New Issue
Block a user