首次上传
This commit is contained in:
@@ -0,0 +1,288 @@
|
||||
using System.Linq;
|
||||
using System.Xml;
|
||||
using Aitex.Core.Common.DeviceData;
|
||||
using Aitex.Core.RT.DataCenter;
|
||||
using Aitex.Core.RT.Event;
|
||||
using Aitex.Core.RT.IOCore;
|
||||
using Aitex.Core.RT.SCCore;
|
||||
using Aitex.Core.RT.Tolerance;
|
||||
using Aitex.Core.Util;
|
||||
|
||||
namespace Aitex.Core.RT.Device.Unit
|
||||
{
|
||||
public class IoFlowMeter : BaseDevice, IDevice
|
||||
{
|
||||
public double Feedback
|
||||
{
|
||||
get
|
||||
{
|
||||
if (_aiFlowValue != null)
|
||||
{
|
||||
ushort value = (ushort)_aiFlowValue.Value;
|
||||
|
||||
double e = value * 1.0 / 65536 * _factor;
|
||||
|
||||
return (e - _physicalMin) * (_rangeMax - _rangeMin) / (_physicalMax - _physicalMin) + _rangeMin;
|
||||
|
||||
//return (e-4) * 40 / 16;
|
||||
|
||||
//return Converter.Phy2Logic((ushort)_aiFlowValue.Value, 0, 40, 0, 0xFFFF/5 );
|
||||
}
|
||||
return 0;
|
||||
}
|
||||
}
|
||||
|
||||
public double FilteredFeedback
|
||||
{
|
||||
get
|
||||
{
|
||||
return _queueData.ToList().Average();
|
||||
}
|
||||
}
|
||||
|
||||
public bool IsWarning
|
||||
{
|
||||
get
|
||||
{
|
||||
return _checkWarning.Result;
|
||||
}
|
||||
}
|
||||
|
||||
public bool IsError
|
||||
{
|
||||
get
|
||||
{
|
||||
return _checkAlarm.Result;
|
||||
}
|
||||
}
|
||||
|
||||
private double _minSetPoint;
|
||||
|
||||
public double MinSetPoint
|
||||
{
|
||||
get
|
||||
{
|
||||
return _minSetPoint;
|
||||
}
|
||||
set
|
||||
{
|
||||
_minSetPoint = value;
|
||||
//if (_aoMin != null)
|
||||
// _aoMin.Value = (short)value;
|
||||
}
|
||||
}
|
||||
|
||||
private double _maxSetPoint;
|
||||
|
||||
public double MaxSetPoint
|
||||
{
|
||||
get
|
||||
{
|
||||
return _maxSetPoint;
|
||||
}
|
||||
set
|
||||
{
|
||||
_maxSetPoint = value;
|
||||
//if (_aoMax != null)
|
||||
// _aoMax.Value = (short)value;
|
||||
}
|
||||
}
|
||||
|
||||
public double MinFlow
|
||||
{
|
||||
get
|
||||
{
|
||||
return _scMinFlow == null ? 0 : _scMinFlow.DoubleValue;
|
||||
}
|
||||
}
|
||||
|
||||
public double MaxFlow
|
||||
{
|
||||
get
|
||||
{
|
||||
return _scMaxFlow == null ? 0 : _scMaxFlow.DoubleValue;
|
||||
}
|
||||
}
|
||||
|
||||
public double WarningTime
|
||||
{
|
||||
get
|
||||
{
|
||||
return _scWarningTime == null ? 0 : _scWarningTime.IntValue;
|
||||
}
|
||||
}
|
||||
|
||||
public double AlarmTime
|
||||
{
|
||||
get
|
||||
{
|
||||
return _scAlarmTime == null ? 0 : _scAlarmTime.IntValue;
|
||||
}
|
||||
}
|
||||
|
||||
public bool IsOutOfTolerance
|
||||
{
|
||||
get
|
||||
{
|
||||
if (MinFlow < 0.01 && MaxFlow < 0.01)
|
||||
return false;
|
||||
|
||||
return (Feedback < MinFlow) || (Feedback > MaxFlow);
|
||||
}
|
||||
}
|
||||
|
||||
public bool EnableToleranceCheck { get; set; }
|
||||
|
||||
|
||||
private AITWaterFlowMeterData DeviceData
|
||||
{
|
||||
get
|
||||
{
|
||||
AITWaterFlowMeterData data = new AITWaterFlowMeterData()
|
||||
{
|
||||
DeviceName = Name,
|
||||
DeviceSchematicId = DeviceID,
|
||||
DisplayName = Display,
|
||||
FeedBack = Feedback,
|
||||
IsWarning = IsWarning,
|
||||
Unit = Unit,
|
||||
IsOutOfTolerance = IsOutOfTolerance,
|
||||
};
|
||||
|
||||
return data;
|
||||
}
|
||||
}
|
||||
|
||||
private AIAccessor _aiFlowValue = null;
|
||||
|
||||
//private DIAccessor _diValve;
|
||||
|
||||
//private DOAccessor _doWarning;
|
||||
//private DOAccessor _doAlarm;
|
||||
|
||||
//private AOAccessor _aoMin;
|
||||
//private AOAccessor _aoMax;
|
||||
|
||||
private SCConfigItem _scMinFlow;
|
||||
private SCConfigItem _scMaxFlow;
|
||||
private SCConfigItem _scWarningTime;
|
||||
private SCConfigItem _scAlarmTime;
|
||||
private SCConfigItem _scEnableTolerance;
|
||||
|
||||
private ToleranceChecker _checkWarning = new ToleranceChecker();
|
||||
private ToleranceChecker _checkAlarm = new ToleranceChecker();
|
||||
|
||||
private RD_TRIG _trigValveOpenClose = new RD_TRIG();
|
||||
|
||||
private int _factor;
|
||||
private int _rangeMin;
|
||||
private int _rangeMax;
|
||||
private int _physicalMin;
|
||||
private int _physicalMax;
|
||||
|
||||
FixSizeQueue<double> _queueData = new FixSizeQueue<double>(20);
|
||||
|
||||
public IoFlowMeter(string module, XmlElement node, string ioModule = "")
|
||||
{
|
||||
var attrModule = node.GetAttribute("module");
|
||||
base.Module = string.IsNullOrEmpty(attrModule) ? module : attrModule;
|
||||
Name = node.GetAttribute("id");
|
||||
Display = node.GetAttribute("display");
|
||||
DeviceID = node.GetAttribute("schematicId");
|
||||
Unit = node.GetAttribute("unit");
|
||||
|
||||
_aiFlowValue = ParseAiNode("aiFeedback", node, ioModule);
|
||||
|
||||
|
||||
int.TryParse(node.GetAttribute("factor"), out _factor);
|
||||
|
||||
string[] range = node.GetAttribute("range").Split(',');
|
||||
int.TryParse(range[0], out _rangeMin);
|
||||
int.TryParse(range[1], out _rangeMax);
|
||||
|
||||
string[] physical = node.GetAttribute("physical").Split(',');
|
||||
int.TryParse(physical[0], out _physicalMin);
|
||||
int.TryParse(physical[1], out _physicalMax);
|
||||
|
||||
_scMinFlow = SC.GetConfigItem($"Modules.{Module}.{Name}.MinFlow");
|
||||
_scMaxFlow = SC.GetConfigItem($"Modules.{Module}.{Name}.MaxFlow");
|
||||
_scWarningTime = SC.GetConfigItem($"Modules.{Module}.{Name}.WarningTime");
|
||||
_scAlarmTime = SC.GetConfigItem($"Modules.{Module}.{Name}.AlarmTime");
|
||||
_scAlarmTime = SC.GetConfigItem($"Modules.{Module}.{Name}.AlarmTime");
|
||||
_scEnableTolerance = SC.GetConfigItem($"Modules.{Module}.{Name}.EnableTolerance");
|
||||
|
||||
MinSetPoint = MinFlow;
|
||||
MaxSetPoint = MaxFlow;
|
||||
}
|
||||
|
||||
public bool Initialize()
|
||||
{
|
||||
DATA.Subscribe($"{Module}.{Name}.DeviceData", () => DeviceData);
|
||||
DATA.Subscribe($"{Module}.{Name}.Feedback", () => Feedback);
|
||||
|
||||
|
||||
return true;
|
||||
}
|
||||
|
||||
public void Terminate()
|
||||
{
|
||||
}
|
||||
|
||||
public void Monitor()
|
||||
{
|
||||
MinSetPoint = MinFlow;
|
||||
MaxSetPoint = MaxFlow;
|
||||
|
||||
_queueData.Enqueue(Feedback);
|
||||
|
||||
//_trigValveOpenClose.CLK = (_diValve == null || _diValve.Value);
|
||||
|
||||
//关闭阀门
|
||||
if (_trigValveOpenClose.T)
|
||||
{
|
||||
_checkWarning.RST = true;
|
||||
_checkAlarm.RST = true;
|
||||
}
|
||||
|
||||
//打开过程中,一直监控
|
||||
if (_trigValveOpenClose.M && _scEnableTolerance.BoolValue)
|
||||
{
|
||||
if (WarningTime > 0.1)
|
||||
{
|
||||
_checkWarning.Monitor(Feedback, MinFlow, MaxFlow, WarningTime);
|
||||
|
||||
if (_checkWarning.Trig)
|
||||
{
|
||||
EV.PostWarningLog(Module, $"Flow meter {Display} feedback out of range");
|
||||
|
||||
}
|
||||
|
||||
//if (_doWarning != null)
|
||||
//{
|
||||
// _doWarning.Value = _checkWarning.Result;
|
||||
//}
|
||||
}
|
||||
|
||||
if (AlarmTime > 0.1)
|
||||
{
|
||||
_checkAlarm.Monitor(Feedback, MinFlow, MaxFlow, AlarmTime);
|
||||
if (_checkAlarm.Trig)
|
||||
{
|
||||
EV.PostAlarmLog(Module, $"Flow meter {Display} feedback out of range");
|
||||
}
|
||||
|
||||
//if (_doAlarm != null)
|
||||
//{
|
||||
// _doAlarm.Value = _checkAlarm.Result;
|
||||
//}
|
||||
}
|
||||
}
|
||||
}
|
||||
|
||||
public void Reset()
|
||||
{
|
||||
_checkWarning.RST = true;
|
||||
_checkAlarm.RST = true;
|
||||
}
|
||||
}
|
||||
}
|
||||
Reference in New Issue
Block a user